Compact 3-Phase RCBO for Distribution Systems
ETL2-63 3P+N series combines thermal-magnetic overload and short-circuit protection with electronic residual current protection in a compact 54 mm, three-module DIN-rail device.
Designed for 400/415 V AC three-phase circuits, it is suitable for residential, commercial, and industrial distribution boards. The series complies with IEC/EN 61009-1. The ETL2-63 offers a rated short-circuit breaking capacity of 6 kA, while the ETL2-63H provides 10 kA. The neutral line is unswitched.
Combined Circuit Protection
Provides earth fault, overload and short-circuit protection in one device.
Three-Phase Configuration
3P+N design for 400/415V AC systems, with an unswitched neutral.
Compact Dimensions
54mm-wide, three-module design for distribution boards.
6kA or 10kA Breaking Capacity
Select ETL2-63 for 6kA or ETL2-63H for 10kA.
Type AC and Type A Options
Select the residual current type according to the installation and connected loads.
B, C and D Tripping Curves
Available for different load characteristics.
Bidirectional Wiring
Line and load connections are interchangeable as specified in the product documentation.
Easy Status Checking
Equipped with a test button and contact position indicator.
DIN-Rail Installation
Suitable for mounting on a 35mm DIN rail.
Accessory Support
Compatible with selected auxiliary contacts, alarm contacts and release devices.
What is a 3P+N RCBO?
A 3P+N RCBO is a residual current circuit breaker with overcurrent protection intended for a three-phase system with a neutral conductor. It combines residual current protection with overload and short-circuit protection. On the ETL2-63(H) 3P+N, the neutral line is unswitched.
What is the difference between ETL2-63 and ETL2-63H?
The ETL2-63 has a rated short-circuit breaking capacity of 6kA, while the ETL2-63H has a rated short-circuit breaking capacity of 10kA.
Is the ETL2-63(H) 3P+N RCBO available in Type A?
Yes. The product series offers Type A and Type AC residual current detection. Please confirm the availability of your required specification before ordering.
Which tripping curves are available for the 3P+N version?
The 3P+N version offers B, C and D tripping curves. The appropriate curve depends on the load characteristics and installation requirements.
Does this RCBO switch the neutral?
No. The neutral line of the ETL2-63(H) 3P+N RCBO is unswitched. If neutral switching or isolation is required, select a device suitable for that requirement.
| Technical Data | |
|
Standard |
IEC/EN 61009-1 |
|
Protection |
Ground fault, overcurrent and short circuit |
|
Type of trip |
Ground fault: Electronic |
|
Overload and short circuit:Thermal-magnetic |
|
|
Residual current type |
AC type: AC residual current |
|
A type: Residual AC and pulsating DC current |
|
|
No. of poles |
3P+N, neutral line is unswitched |
|
Insulation voltage (Ui) |
500V |
|
Rated voltage (Ue) |
400/415V~ |
|
Rated currents (In) |
6, 10, 16, 20, 25, 32, 40, 50, 63A |
|
Rated sensitivity currents (IΔn) |
10, 30, 100, 300mA |
|
Residual current off-time under IΔn |
≤0.1s |
|
Rated residual making and breaking capacity (IΔm) |
500A (In ≤ 50A); 10In (In > 50A) |
|
Rated frequency |
50/60Hz |
|
Rated short-circuit capacity (Icn) |
ETL2-63: 6kA; ETL2-63H: 10kA |
|
Energy limiting class |
3 |
|
Rated impulse withstand voltage (Uimp) (1.2/50μs) |
4kV |
|
Dielectric test voltage |
2kV (50/60Hz, 1 min.) |
|
Fire resistance (glow-wire test) |
960 ± 15°C (enclosure); 650 ± 10°C (handle) |
|
Thermal tripping characteristics |
1.13In: no tripping within an hour; 1.45In: tripping within an hour |
|
Instantaneous tripping characteristics |
B: 3In–5In; C: 5In–10In; D: 10In–20In |
|
Electrical life |
4,000 cycles |
|
Mechanical life |
8,000 cycles |
|
Contact position indicator |
Green OFF / Red ON |
|
Protection degree |
IP20 |
|
Ambient temperature |
−25°C to +55°C |
|
Storage temperature |
−30°C to +70°C |
|
Top terminals connection type |
Cable / Pin-type busbar |
|
Bottom terminals connection type |
Cable / Pin-type / Fork-type busbar |
|
Max. Top terminal size for cable |
25mm² |
|
Max. Bottom terminal size for cable |
25mm² |
|
Max.Top tightening torque |
2.0N·m |
|
Max. Bottom tightening torque |
2.5N·m |
|
Neutral load cable |
Blue, 455mm length, 4mm²; other lengths available upon request |
|
Installation |
Mounting on 35mm DIN rail |
|
Wiring method |
Bi-Directional |
|
Auxiliary Contact |
Yes |
|
Auxiliary & Alarm Contact |
Yes |
|
Shunt Release |
Yes |
|
Shunt Release & Auxiliary Contact |
Yes |
|
Voltage Loss Release |
Yes |
|
Over-voltage Release |
Yes |
|
Undervoltage Release |
Yes |
|
Over-undervoltage Release |
Yes |